Files
esphome/rack_2.yaml

191 lines
4.7 KiB
YAML

substitutions:
duct_fan_pin: GPIO13
duct_fan_name: Rack 2 Duct Fan Speed
duct_fan_spd_target_in_name: Rack 2 Duct Fan Target Speed In
duct_fan_spd_target_out_name: Rack 2 Duct Fan Target Speed Out
# duct_fan_channel: "0"
duct_fan_pwmfreq: 5000Hz
duct_fan_off_spd: "0.0"
duct_fan_lo_spd: "10.0"
duct_fan_hi_spd: "100.0"
wall_fan_pwr_pin: GPIO21
wall_fan_pwr_name: Rack 2 Wall Fan Power
wall_fan_spd_pin: GPIO22
# wall_fan_spd_channel: "2"
wall_fan_spd_pwmfreq: 25000Hz
wall_fan_spd_name: Rack 2 Wall Fan Speed
wall_fan_tach_pin: GPIO23
wall_fan_tach_id: wall_fan_tach_id
wall_fan_tach_name: Rack 2 Wall Fan Tach
dallas_pin: GPIO32
dallas_in_addr: "0x1D02131D6063AA28"
dallas_in_name: Rack 2 Temp In
dallas_out_addr: "0x1D01143296570128"
dallas_out_name: Rack 2 Temp Out
dallas_update_interval: 30s
globals:
- id: duct_fan_off_spd
type: float
initial_value: ${duct_fan_off_spd}
- id: duct_fan_lo_spd
type: float
initial_value: ${duct_fan_lo_spd}
- id: duct_fan_hi_spd
type: float
initial_value: ${duct_fan_hi_spd}
esphome:
name: rack_2
platform: ESP32
board: esp32doit-devkit-v1
wifi:
ssid: "kungle-ot"
password: "ThingsWelcomeToKungle"
manual_ip:
static_ip: 192.168.37.76
gateway: 192.168.37.1
subnet: 255.255.255.0
# Enable fallback hotspot (captive portal) in case wifi connection fails
ap:
ssid: "Server 2 Fallback Hotspot"
password: "kRzC55vFjigT"
captive_portal:
# Enable logging
logger:
level: DEBUG
# Enable Home Assistant API
api:
ota:
switch:
- platform: gpio
pin: ${wall_fan_pwr_pin}
name: ${wall_fan_pwr_name}
- platform: template
name: Thermostat On
id: thermostat_on_id
optimistic: true
output:
- platform: ledc
pin: ${duct_fan_pin}
id: duct_fan_output_id
channel: 0
frequency: ${duct_fan_pwmfreq}
- platform: ledc
pin: ${wall_fan_spd_pin}
id: wall_fan_spd_id
channel: 2
frequency: ${wall_fan_spd_pwmfreq}
fan:
- platform: speed
id: duct_fan_spd_id
output: duct_fan_output_id
name: ${duct_fan_name}
- platform: speed
output: wall_fan_spd_id
name: ${wall_fan_spd_name}
dallas:
- pin:
number: ${dallas_pin}
mode: INPUT_PULLUP
update_interval: ${dallas_update_interval}
sensor:
- platform: pulse_counter
pin:
number: ${wall_fan_tach_pin}
mode: INPUT_PULLUP
unit_of_measurement: 'RPM'
name: ${wall_fan_tach_name}
update_interval: 10s
filters:
- multiply: 0.5
- platform: dallas
address: ${dallas_in_addr}
name: ${dallas_in_name}
- platform: dallas
address: ${dallas_out_addr}
name: ${dallas_out_name}
id: dallas_out_id
number:
- platform: template
id: duct_fan_spd_target_in
name: ${duct_fan_spd_target_in_name}
optimistic: true
min_value: ${duct_fan_lo_spd}
max_value: ${duct_fan_hi_spd}
step: 1
- platform: template
id: duct_fan_spd_target_out
name: ${duct_fan_spd_target_out_name}
min_value: ${duct_fan_off_spd}
max_value: ${duct_fan_hi_spd}
step: 1
set_action:
then:
lambda: |-
float lo;
float hi;
float curtemp;
float newspd;
lo = id(thermostat_out_id).target_temperature_low;
hi = id(thermostat_out_id).target_temperature_high;
curtemp = id(dallas_out_id).state;
if ((curtemp < lo) || (id(thermostat_on_id).state == false)) {
auto call = id(duct_fan_spd_id).turn_off();
call.perform();
return id(duct_fan_off_spd);
}
if (curtemp > hi) {
newspd = id(duct_fan_hi_spd);
} else {
// Set newspd to same linear proportion of spd range as current temp is of temp range
newspd = id(duct_fan_lo_spd) + (id(duct_fan_hi_spd) * (curtemp - lo) / (hi - lo));
}
auto call = id(duct_fan_spd_id).turn_on();
call.set_speed(newspd);
call.perform();
return newspd;
# Dual-point thermostat
climate:
- platform: thermostat
id: thermostat_out_id
name: Rack2 Out
sensor: dallas_out_id
visual:
min_temperature: 60 °F
max_temperature: 100 °F
temperature_step: 1
default_mode: auto
default_target_temperature_low: 75 °F
default_target_temperature_high: 100 °F
min_cooling_off_time: 60s
min_cooling_run_time: 60s
min_heating_off_time: 60s
min_heating_run_time: 60s
min_idle_time: 60s
heat_action:
- logger.log: "Turning off Rack2 Thermostat"
- switch.turn_off: thermostat_on_id
idle_action:
- logger.log: "Turning on Rack2 Thermostat"
- switch.turn_on: thermostat_on_id
cool_action:
- logger.log: "WARNING: Rack2 Thermostat has hit high temp!"
- switch.turn_on: thermostat_on_id
#TODO - provide some kind of warning / action here